                  ZW-LZ series Insulation type metal tube rotameter Using the principle of variable area measurement, …

                  Description:

                  Productoverview:

                  ZW-LZ series Insulation type metal tube rotameter Using the principle of variable area measurement, suitable for measuring of liquid gas. All metal structure, indicating type, electric remote type, corrosion type, pressure type, explosion-proof type. With 0-10mA, 4-20mA standard analog signal and output instructions. The accumulation of digital communication, site modification parameter, function of different power supply modes, with a magnetic filter and special specifications. Widely used in petroleum, chemical, power, pharmaceutical, food, water treatment, etc.. The complex, harsh environmental conditions, the flow measurement process and various medium conditions in.

                  Two, work principle:

                  ZW-LZ series insulation type metal tube rotameter is the medium to be measured through a conical measuring tube float from upper and lower ends of the differential pressure generated form the upward force, when the float was immersed in a fluid on the lift is greater than the weight of the float, the float will rise, annulus area increases, the annulus fluid velocity decreased immediately float the lower end of the differential pressure is reduced, to float upward force also decreases with, until the lift is equal to the weight of the float when immersed in a fluid, the float will stabilize at a certain height. The float position that corresponds to the size of the measured medium flow. A built-in magnet, the float with the medium moves up and down, with the movement of the float magnetic field changes.

                  A, for in situ, by rotary magnetic float and the local indicator in the inner magnetic coupling, rotate, and drives the pointer, through the dial indicates the size of the flow.

                  B, the intelligent, by a solid state magnetic sensor intelligent indicator in the magnetic field will change into electrical signal output by A/D transform, D/A microprocessor, LCD liquid crystal display to show the size and cumulative flow flow.

                  Three, conversion indicator:

                  The converter is actually the height conversion taper pipe float into the corresponding volume scale. From the output signal: local display and remote signal output type:

                  1, local display type: by in situ indicator in the follow-up magnetic float and the inner magnetic coupling, and rotate, and the electric pointer by dial indicating the flow.

                  2, intelligent remote type, by the intelligent indicator in the follow-up magnetic float and the inner magnetic coupling, rotate, and drives the magnet and the sensing pointer through a magnetic sensor magnetic field change into electrical signals by A/D conversion, digital filter, D/ microprocessor, A output, LCD liquid crystal display, to show the instantaneous flow and cumulative flow rate.

                  Four, instrument structure:

                  ZW-LZ series insulation type metal tube rotameter is mainly composed of a measuring device and the indicator consists of two parts, according to the different ways of connection can be divided into vertical and horizontal installation two installation.

                  Measuring device part

                  Basic type: wetted parts material 0Cr19Ni9, suitable for liquid measurement.

                  Anticorrosive lining: PTFE, suitable for measuring the corrosive medium.

                  Jacket: for medium need insulation or cooling occasions, jacket flange DN15, PN1.6.

                  Damping type: suitable for gas measurement.

                  Indicator

                  Instructions: instructions for instantaneous flow field.

                  Transmission type: DC signal output of 4 ~ 20mA, realize the remote transmission function.

                  Alarm type: the need for alarm.

                  Five, main features:

                  1, all metal structure design, strong, simple, high pressure resistance, high temperature resistance, corrosion resistance, long service life;

                  2, a short trip, the total height of 250mm, easy to install;

                  3, mechanical pointer instructions LCD liquid crystal display instantaneous flow, instantaneous flow, cumulative flow;

                  4, intelligent indicator, using foreign Zui new signal processing chip, modular design, no hysteresis;

                  5, data recovery, data backup, power down protection and fault self diagnosis function;

                  6, HART type indicator, two-wire 24VDC power supply, 4-20mA standard current signal output of HART protocol stack;

                  7, through the HART communication manipulator configuration and parameters can be adjusted;

                  8, with the PC serial connection, through the Windows program, to achieve on-site calibration of the instrument;

                  9, can be used in flammable and explosive occasions;

                  10, vertical and horizontal, upper lower, bottom side, side into the side such as the installation of a variety of forms, flange or threaded connection.

                  Six, technical parameters:

                  1, measurement range: water 2.5 ~ 100000l/h (20 C)

                  2, range: 10:1

                  3, 1.0, 1.5, precision grade: 2.5

                  4, working pressure: DN15 DN25, DN50, PN4.0MPazui, DN80, DN100 10.0MPa PN1.6MPazui 6.4MPa

                  5, medium temperature: -40 to 300 DEG C

                  6, medium viscosity: DN15: <5mPa - s eta (F15.1 ~ F15.3)

                  <30mPa - S (F15.4 - F15.8)

                  DN25: <250mPa - s.

                  DN50: <300mPa - S - DN150.

                  7, the ambient temperature: LCD type: -40 to 85 DEG C

                  Pointer type: -40 to 120 DEG C

                  8, connection: flange (executive standard DIN2501 or as required by standard flange manufacturing)

                  9 meter height: 250mm

                  10, cable interface: M20*1.5

                  11, power supply: 24VDC two-wire 4 ~ 20mA or 85 ~ 265VAC 50/60Hz (remote type)

                  12, alarm output: alarm relay output lower or upper limit of instantaneous flow (contact capacity Zui 5A-250VAC) or open collector output (internal impedance Zui 100mA-30VDC 100 ohm).

                  13, the cumulative output pulse: pulse output, Zui interval of every 10 seconds a pulse (AC) or a pulse every 50 milliseconds.

                  14, double liquid crystal display: LCD display, display the instantaneous flow and cumulative flow.

                  15: Exia II CT4, explosion-proof.

                  16, the measuring tube material: 316 stainless steel (common type) or Teflon liner (corrosion type).

                  Seven, product maintenance:

                  1, in the process of long-term use, the pipeline inevitably there will be ferromagnetic impurity adsorption on the float, it will float stuck or affect the measurement accuracy, from time to time to clean the sensor float; if the installation of magnetic filters should be cleaned regularly.

                  2, the instrument indicator with electronic components, instrument wiring or demolition of housing, to housing screws, must ensure sealing, prevent impurities, or other material into the water, and also to ensure reliable earthing of the meter casing.

                  3, the instrument is installed, in use, should pay attention to:

                  When the valve is opened to avoid the formation of pressure shock makes the float slamming limiting device, causing damage to the instrument, slowly open the valve!

                  The measurement of gas meter is equipped with gas damper, Zui to decrease the float concussion; to ensure the stability of the float, a throttle valve can be installed in the instrument export.

                  4, for the remote type instrument, we must first ensure that the instrument wiring correctly, keeps power; for dangerous situations, must choose the explosion-proof, and the installation and use of proof required by the.

                  Eight, installation notes:

                  1, before installation flowmeter must be welding slag, clean the impurities in pipelines.

                  Part 2, erect flowmeter must be perpendicular to the ground installation inclination of not more than 5 degrees. Otherwise it will affect the measurement accuracy.

                  3, in order to ensure the accuracy of flowmeter, should increase the straight section of not less than 10xDN in the inlet side of the outlet end of the flowmeter, not less than 5 * DN straight pipe, measurement control valve must be installed in the downstream of the flowmeter.

                  4, if the measured medium is a pulsating flow or two-phase flow buffer should be large, installed in the upstream of the flowmeter to eliminate or weaken the fluctuation, to ensure the flow of medium is single-phase stable, at the same time, suggested using damping type flowmeter.

                  5, the medium is dirty or containing magnetic particles, recommended to install filters or filter in the upstream of the magnetic flowmeter.

                  6, vibration flowmeter shall be installed properly supporting pipeline or reduce the axial load of the flowmeter, otherwise should increase the support of fixed flowmeter.

                  7, in order to facilitate the maintenance of magnetic flowmeter, filter cleaning and user line maintenance, recommended as shown in the figure Shuo bypass pipe.

                  8, when the flowmeter is used to measure the gas, should ensure that the pressure loss in pipeline working pressure not less than 5 times the meter, the meter can make stable normal operation.

                  9, the electric remote alarm and meter limit switch before use, open the instrument cover, according to the correct wiring wiring diagram.

                  10, according to the instrument indicator in the warning signs, remove the vibration resistance of the moving parts to prevent float transport, then use the restored instrument.

                  Troubleshooting nine fault:

                  1, check the alarm set value size SU.

                  2, check the deviation set D value can not be too large.

                  3, FUN function, logic function is correct. HA-A said the upper limit is logical. LA-A said the lower limit is.

                  4, circuit board failure, replace the board.

                  5, if the lcd barcode indicates the correct output, no action, the cathode can check the external power and external power supply is connected with the anode of instrument power supply.

                  If the wobble in use, according to the jitter amplitude to determine what kind of amplitude jitter. Divided into mild and moderate jitter jitter jitter and jitter.

                  1, a slight jitter due to fluctuations caused by the media. Can be used to increase the damping of the way to overcome.

                  2, moderate jitter caused by medium flow state: general. For general gas as the medium pressure instability caused by.The regulator or stabilizer to overcome or increase the damping of gas meter.

                  3, severe jitter: mainly due to medium gas pulsation, operation pressure instability or give users pressure, temperature, flow meter and the actual state does not have large differences over range instrument.

                  Ten, the measuring range and the pressure loss:

                  Decay path

                  Common path

                  measuring range

                  Zui high pressure loss

                  DN (mm)

                  DN (mm)

                  The air (m3/h)

                  Water (L/h)

                  The air (KPa)

                  Water (KPa)

                  Fifteen

                  Fifteen

                  0.05-0.5

                  1.6-16

                  Seven

                  Six point four

                  0.07-0.7

                  2.5-25

                  Seven point one

                  Six point five

                  0.11-1.1

                  4.0-40

                  Seven point two

                  Six point five

                  0.18-1.8

                  6.0-60

                  Seven point three

                  Six point six

                  0.28-2.8

                  10-100

                  Seven point five

                  Six point six

                  0.40-4.0

                  16-160

                  Eight

                  Six point eight

                  0.70-7.0

                  25-250

                  Ten point eight

                  Seven point two

                  1.00-10

                  40-400

                  Ten

                  Eight point six

                  1.60-16

                  60-600

                  Fourteen

                  Eleven point one

                  Twenty-five

                  -

                  80-800

                  -

                  Fourteen

                  Twenty-five

                  3.00-30

                  100-1000

                  Seven point seven

                  Seven

                  4.50-45

                  160-1600

                  Eight point eight

                  Eight

                  7.00-70

                  250-2500

                  Twelve

                  Ten point eight

                  11-110

                  400-4000

                  Nineteen

                  Fifteen point eight

                  Fifty

                  -

                  500-5000

                  -

                  Sixteen point two

                  Fifty

                  18-180

                  600-6000

                  Eight point six

                  Eight point one

                  25-250

                  1000-10000

                  Ten point four

                  Eleven

                  Eighty

                  40-400

                  1600-16000

                  Twelve point six

                  Seventeen

                  Eighty

                  50-500

                  2000-20000

                  Fifteen point five

                  Six point three

                  One hundred

                  75-750

                  2500-25000

                  Seventeen Point Two

                  Eight point one

                  One hundred

                  100-1000

                  4000-40000

                  -

                  Nine point five

                  One hundred and twenty-five

                  160-1600

                  6000-60000

                  -

                  Ten

                  One hundred and twenty-five

                  250-2500

                  8000-80000

                  -

                  Sixteen

                  One hundred and fifty

                  -

                  10000-100000

                  -

                  Twenty


                  300-3000

                  12-120m3/h

                  -

                  Twenty


                  400-4000

                  15-150m3/h

                  -

                  Twenty-five

                  Eleven, the selection of encoding:

                  Specification code

                  Encoding instructions

                  The name of the factory

                  ZW

                  Zhongwei control

                  Instrument types

                  LZ

                  Metal tube rotameter

                  structural style

                  /

                  In the next

                  H1

                  The left into the right

                  H2

                  Right into the left out

                  AA

                  The side into the side

                  LA

                  The bottom side

                  S

                  Threaded connection

                  M

                  Clamp connection (sanitary polishing tube)

                  Size code

                  - XXX

                  Cases: Fifteen Express DN15

                  The measuring tube material

                  R1

                  1Cr18Ni9Ti , Three hundred and four

                  R0

                  0cr18Ni12M02Ti , Three hundred and sixteen

                  RL

                  316L

                  RP

                  (PTFE F-lined )

                  Ni

                  (Hasloy Hastelloy C)

                  Ti

                  (TitHXium titanium alloy )

                  Media type

                  L

                  liquid

                  G

                  Gas

                    working temperature 

                  H1

                  - 40 C -100 C

                  H2

                  - 80 C -250 C

                  Rated pressure

                  One point six

                  1.6MPa

                  Four

                  4.0MPa

                  Sixteen

                  16MPa

                  Twenty-five

                  25MPa

                  Additional structure

                  O

                  nothing

                  Z

                  Damping type

                  T

                  Jacket

                  H

                  High temperature type

                  Y

                  High pressure type

                  Form indicator

                  M1

                  Local indication

                  M2

                  Intelligent

                  M3

                  Intelligent ( Flameproof )

                  The output signal in the communication

                  N

                  nothing

                  A

                  4-20mA

                  H

                  4-20mA+Hart

                  Alarm controller

                  K1

                  The upper limit alarm

                  K2

                  Alarm

                  K12

                  The upper and lower limit alarm

                  Explosion proof type

                  E1

                  Intrinsically safe EX IaCT5 Square shell

                  E2

                  Flameproof EXiibt4 Park Housing

                  Power supply

                  Zero

                  24VDC (can be omitted )

                  Two

                  220VAC

                  Three

                  Three point six Volt lithium battery

                  12, design selection and ordering information:

                  1, please provide the pipe size, wall thickness, material requirements and accuracy requirements;

                  2, please provide the liquid or gas, such as the name, commonly used commonly used temperature, working pressure, common flow, density, viscosity etc.;

                  3, choose anti-corrosion type, should indicate the measured corrosion and concentration etc.;

                  4, if there are special to show, please contact our sales department.

                  Customer service service commitment:

                  1, our series of metal tube flowmeter series product quality problems within twelve months, responsible for free maintenance.

                  2, the warranty period if the products of our company have any quality problems, our company is responsible for free repair or replacement.

                  3, the warranty period if the user use undeserved, cause damage to the product, our company is responsible for the maintenance, collect the damaged parts cost.

                  4, after the warranty period of product quality problems, our company is responsible for the maintenance, collect the damaged parts cost.

                  5, if the user needs to our service, our company in the province of the user service personnel arrived at the scene within 12 hours, arrived at the scene 48 hours outside users.